Annual Flow Tests For Diesel-Driven Fire Pumps

Annual flow tests are a critical component of the inspection, testing, and maintenance procedures outlined by NFPA 20, and 25 for diesel-driven fire pumps. These tests are designed to assess the pump system’s overall performance, ensuring it can deliver the required flow rates and pressures during a fire emergency. Here’s a detailed look at the annual flow testing requirements according to NFPA 20:

1. Purpose of Annual Flow Tests:

    The primary objectives of annual flow tests include:

    • Verification of Capacity:
      • Confirm that the fire pump can deliver the designed flow rates and pressures as specified during its initial design.
    • Identification of Issues:
      • Identify any deficiencies or problems in the system that may affect its performance.
    • Compliance Assurance:
      • Ensure compliance with NFPA 20 standards and local fire codes.

    2. Testing Procedure:

      NFPA 20 provides specific guidelines on how to conduct annual flow tests:

      • Test Duration:
        • The flow test should typically be conducted for a duration of 30 minutes or as specified by the authority having jurisdiction (AHJ).
      • Pressure Measurements:
        • Measure and record the pressures at the pump discharge, as well as at representative points in the system, such as remote hose stations.
      • Flow Measurements:
        • Measure and record the flow rates during the test, ensuring that they meet or exceed the required values.
      • Test Conditions:
        • The test should be conducted under normal operating conditions, including utilizing the available water supply source.

      3. Inspection of System Components:

        During the annual flow test, it is also an opportunity to inspect various components of the fire pump system:

        • Pump and Engine Condition:
          • Evaluate the overall condition of the pump and diesel engine, ensuring there are no signs of wear, damage, or corrosion.
        • Piping and Valves:
          • Inspect the suction and discharge piping, along with valves, for any leaks, corrosion, or obstructions.
        • Control Panel Verification:
          • Confirm that the control panel is functioning correctly and that alarms and signals are working as intended.

        4. Documentation:

          Documenting the results of the annual flow test is crucial for maintaining a comprehensive record of the fire pump system’s performance. The documentation should include:

          • Test Date and Time:
            • Record the date and time of the flow test.
          • Test Parameters:
            • Document the pressure readings, flow rates, and any deviations from the specified values.
          • Any Issues Identified:
            • If any issues or deficiencies are identified during the test, document them for immediate corrective action.

          5. Corrective Actions:

            If the annual flow test reveals any discrepancies or issues, prompt corrective actions should be taken to address and rectify them. This may involve repairs, replacements, or adjustments to ensure the system’s optimal functionality.

            Annual flow tests as per NFPA 20 standards are instrumental in confirming the reliability and effectiveness of diesel-driven fire pumps. Conducting these tests diligently, documenting the results, and taking corrective actions when necessary contribute to maintaining a robust fire protection system, thereby enhancing overall building safety.

            Build Your Custom Fire Safety Plan

            At Red Seal Fire Protection, we understand that every property has unique fire safety needs. Our experts work closely with you to assess your specific requirements, risks, and budget, creating a tailored fire safety plan that provides comprehensive protection while aligning perfectly with your business operations and goals.