A fire watch is the standard alternative measure in Ontario when a fire alarm, sprinkler or fire pump is out of service and the building stays occupied. Ontario Fire Code Division B Section 2.8 requires your fire safety plan to set alternative measures for occupants during any shutdown of fire protection equipment. NFPA 25 Chapter 15 calls a sprinkler shutdown an impairment and lists a fire watch among the recommended actions. The watch is a trained person with no other duties who patrols the area, can call the fire department and keeps a log until the system is back.
When is a fire watch required in Ontario?
Okay, so the big thing is this: a fire watch is required when a fire protection system the building relies on is out of service and people are still inside. The fire alarm is the usual trigger. A closed sprinkler valve, a fire pump that will not start or a water main shut off by the municipality trigger it the same way.
The reason being, the building was approved on the basis that those systems work. Ontario Fire Code Division B Section 2.8 requires the fire safety plan to spell out alternative measures for occupants during any shutdown of fire protection equipment. A fire watch is the measure almost every plan names, and NFPA 25 Chapter 15 lists it among the recommended actions for a sprinkler impairment.
| Situation | Where the requirement comes from | What the fire watch covers |
|---|---|---|
| Fire alarm system out of service (panel failure, damaged wiring, power loss) | Ontario Fire Code Division B Section 2.8 (alternative measures) and Section 6.3 | Every occupied floor, with a way to warn occupants by voice or horn |
| Sprinkler control valve closed for a repair or a leak | NFPA 25 Chapter 15 (impairments) | The area fed by that valve |
| Fire pump out of service or unable to start | NFPA 25 Chapter 15 | The whole protected building |
| Municipal water main shut off or pressure lost | NFPA 25 Chapter 15 (emergency impairment) | The whole sprinklered building |
| Dry pipe system tripped or drained for a freeze repair | NFPA 25 Chapter 15 | The dry zone: loading dock, attic or parking level |
| Hot work such as welding, cutting or grinding | The hot work permit and your fire safety plan | The work area during the job and for a set period after |
| Testing that takes the alarm or sprinklers offline for hours | Ontario Fire Code Division B Section 2.8 | The affected area for the length of the test |
So, as opposed to a judgment call at 5 p.m. on a Friday, the trigger is written down in advance. If your plan does not say when a fire watch starts, that is the first thing to fix. Our fire safety plan update guide shows where it goes.
Who can perform a fire watch and what do they actually do?
The fire watch is a person, not a camera. The person has to be trained on the building and have no other duties while on watch. They carry a phone or radio that reaches 911, and they need a way to warn occupants if the alarm cannot.
Your superintendent, a security guard or a hired fire watch service can all fill the role. The fire safety plan names who.
What they do is walk. They patrol the area that lost protection, looking and smelling for smoke, checking that exits are clear and watching anything hot. Neither the Fire Code nor NFPA 25 fixes the time between rounds, so the plan or the fire department’s written direction sets it.
Where neither does, I would say a continuous patrol with a logged round at least every hour is the common expectation. I have stood in a plant in Tecumseh at 11 p.m. with a maintenance lead holding a clipboard, because a forklift hit a branch line at 4 p.m. and the sectional valve had to stay closed overnight. He walked the warehouse once an hour until we had the pipe capped and the valve open at 7 the next morning.
So the person on watch needs three things: training, a phone and a log. Everything else is walking.
What do you have to log during a fire watch?
One thing to know: the log is the proof. Without it, the fire watch happened only in someone’s memory. Each entry records the date, the time of the round, the areas walked, the name of the person and anything found.
The log also records the start of the impairment: what went out of service, when, and who was told. NFPA 25 Chapter 15 requires the impaired system to be tagged at the riser or panel, and the tag and the log should match. When the system comes back, the log closes with the time, who restored it and the test that proved it.
Ontario Fire Code Division C Section 1.1.2 requires two years of records, and Windsor Fire & Rescue Services asks to see two years on site. So the finished log goes in the binder, as opposed to the glove box of the truck.
Who has to be notified when a fire alarm is out of service?
NFPA 25 Chapter 15 sets the notification list for a sprinkler impairment, and it is the right list for a fire alarm out of service too. The fire department, the insurer, the building owner, the monitoring station and the occupants all get a call. The monitoring station matters twice.
If the alarm is down, the station needs to know it will not receive signals. If a sprinkler valve is closed, the station needs to know the supervisory signal is expected.
How you notify the fire department varies by municipality. Windsor Fire & Rescue Services, Chatham-Kent Fire & Rescue and the Essex County fire services each have their own practice for impairment notification. Confirm the number or email with your local fire prevention office and write it into the plan.
So what that means is five phone calls at the start and five at the end. Keep the numbers on the first page of the fire safety plan where the person on watch can find them.
How do you shorten a fire watch?
A fire watch ends when the system is back in service and tested. The reason being, the watch stands in for the system, and only a working system replaces it. Everything you do to speed up the repair shortens the watch by the same amount.
Three things make the biggest difference. First, call a technician the moment the system goes down, as opposed to the next morning. Red Seal responds within 2 hours in Windsor-Essex and Chatham-Kent, and same-day in Sarnia-Lambton and London.
Second, keep a stocked spare sprinkler cabinet on site. A sheared sprinkler is a repair measured in minutes with the right head in hand, and a multi-day impairment without it. Third, make sure every control valve is tagged and supervised, so a closed valve is found the same day; the closed valve problem explains why that one matters most.
Fire alarm faults follow the same logic. A panel that cannot sound an alarm is a fire watch until it can, so a trouble signal is a technician call. Our emergency fire alarm repair page covers the call, and what to do about a fire alarm trouble signal covers the first hour.
So the fire watch is a cost you control. Fast call, right parts, system back on test, log closed.
Frequently asked questions
When is a fire watch required for a fire alarm out of service?
A fire watch is required as soon as the fire alarm cannot detect or signal a fire and the building stays occupied. Ontario Fire Code Division B Section 2.8 requires your fire safety plan to set the alternative measures for that shutdown, and a fire watch is the standard measure. It continues until the system is repaired, tested and back on line with the monitoring station.
Can building staff perform a fire watch?
Yes, if they are trained on the building, have no other duties while on watch, can reach 911 and keep a log. The fire safety plan names who does it. A hired fire watch service is an option when you do not have the staff to cover the hours. The fire department is entitled to ask who is on watch and how they were instructed.
How often does a fire watch have to do rounds?
Neither the Ontario Fire Code nor NFPA 25 sets a fixed time between rounds. The fire safety plan or the fire department’s written direction sets it for your building. Where nothing is written, a continuous patrol with a logged round at least every hour is the common expectation.
Does a sprinkler system impairment always need a fire watch?
NFPA 25 Chapter 15 requires an impairment to be tagged, the listed parties notified and the recommended actions considered. A fire watch is one of those actions and the usual choice when the building stays occupied. For a short planned impairment with a technician on site, the fire safety plan may set a lighter measure, and the fire department is entitled to ask about it.
Who do I call first when the fire alarm goes down in Windsor?
Call your fire protection contractor and your monitoring station first. Then call Windsor Fire & Rescue Services through the number your fire safety plan lists for impairments, followed by your insurer and the building owner. Start the fire watch while you make the calls. Red Seal answers emergency calls in Windsor-Essex within 2 hours.
Is a fire watch worth the labour if the repair is tomorrow?
The watch is required for every hour the system is down, so the question is how many hours you pay for. A watch that starts at 4 p.m. and ends at 7 a.m. is one night of a superintendent’s time, and the same fault left for a Monday call-out is three nights with a log for each.