Your Fire Safety Plan Is Probably Out of Date: The Annual Update Ontario Fire Departments Expect

Ontario Fire Code Division B Section 2.8 requires a fire safety plan in any building with a fire alarm, sprinkler or standpipe system, and in most assembly, care and larger residential buildings. The plan has to be approved by the Chief Fire Official and kept current: a review at least every 12 months, and after any change to the building, its systems or its people. Windsor Fire & Rescue Services asks for the plan’s contact pages to be updated every year and emailed as a PDF to fpinspectors@citywindsor.ca. A plan nobody has opened since approval is out of date.

What are the fire safety plan requirements in Ontario?

Okay, so first things first. If your building has a fire alarm, a sprinkler system or a standpipe, Ontario Fire Code Division B Section 2.8 requires a fire safety plan. The same section captures assembly buildings, care buildings and residential buildings above a set size.

The reason being, those are the buildings where people depend on staff and systems to get out. The plan tells your staff what to do in the first minutes of an alarm. It also tells Windsor Fire & Rescue Services how the building is laid out and protected.

So, as opposed to a binder you keep because an inspector asked once, the plan is a Fire Code requirement for most commercial and multi-residential buildings in Windsor-Essex. If you are not sure your building is captured, the fire department can tell you. Our parent guide to fire safety plans covers what a plan is from the ground up.

What has to be in the plan for fire safety plan approval?

The big thing is that the plan is approved for your building as it stands on the day you submit it. Section 2.8 sets out the contents. The plan covers emergency procedures for occupants, the names and duties of supervisory staff, and staff instruction.

It also covers fire drills, control of fire hazards and maintenance of the fire protection systems. It sets out alternative measures when a system is shut down. And it includes drawings showing where the fire protection is.

Fire safety plan approval sits with the Chief Fire Official. In Windsor that is Windsor Fire & Rescue Services. In Tecumseh, LaSalle, Lakeshore, Leamington, Kingsville, Amherstburg and Essex, each municipality runs its own fire service and approves plans for its own area.

So the approved plan is a snapshot. It is accurate on the day it is stamped. It starts drifting the next morning.

Why does an approved fire safety plan go stale within a year?

Every section of the plan points at something that changes. Supervisory staff change jobs. Tenants move in and out.

A sprinkler zone gets added for a new mezzanine. The monitoring station changes its phone number. None of those changes update the binder on their own.

I have read plans in valve rooms that still named a superintendent who retired years earlier. His old cell number was listed as the after-hours contact. The plan had been approved, and it was no use at 2 a.m.

So what that means is the approval is the start of the plan’s life. The annual review is how it stays alive. The Fire Code requires a review at intervals of not more than 12 months, so the plan keeps up with the building.

What does the fire department expect you to update every year?

One thing to know: the fire prevention officer is entitled to ask for a current plan at any inspection. The Code also requires you to keep records of your fire drills and staff instruction. Windsor Fire & Rescue Services goes a step further for business licence holders.

Its annual licence items include a fire safety plan review for buildings with more than 30 seats. It also asks that the plan’s contact pages be updated every year and emailed as a PDF to fpinspectors@citywindsor.ca. Questions about what Windsor wants can go to firesafety@citywindsor.ca.

Fire drills live in the same section of the Code. Most buildings need a drill at least once every 12 months, and vulnerable occupancies such as retirement homes need one monthly. Each drill goes in your records, and Windsor asks to see two years of records on site.

So the yearly package is three things: updated contact and staff pages, a drill on record, and a plan that still matches the building. How long to keep those records is covered in our guide to fire inspection records retention in Ontario.

How do you review a fire safety plan in 20 minutes?

Pull the binder, open it to page one, and walk through the table below with a pen. I would say 20 minutes covers a single-tenant commercial building. A multi-residential tower with several supervisory staff takes longer, and that is fine.

Section of the planWhat usually changed since approvalWhat to do
Building and owner contactsOwnership, property manager or after-hours number changedCorrect the names and numbers; this is the page Windsor asks for every year
Supervisory staff and dutiesThe superintendent or designated staff left and nobody was reassignedName the current people and walk them through their duties
Emergency procedures and posted noticesFloor postings are missing, faded or show the wrong assembly pointReplace the postings so they match the plan
Fire protection systems and schematic drawingsA system was added, replaced or re-zoned, or a panel was swappedUpdate the system list and drawings from your latest inspection report
Alternative measures during a shutdownThe plan says fire watch but nobody knows who does itConfirm who performs the fire watch and how the fire department is notified
Fire drill and staff instruction recordsThe last drill is more than 12 months oldBook a drill, run it, file the record
Monitoring station and contractor contactsThe monitoring company or fire protection contractor changedUpdate the contact and account details

If a change in that table affects how the building is protected, send the revised pages to the fire department for approval. Do not quietly swap them into the binder. A re-zoned sprinkler system or a new fire alarm panel is a change to the plan, as opposed to a typo.

The alternative measures row deserves its own look. Our fire watch guide explains what that section needs to say.

So the review is mostly names, numbers and drawings. The fire system inspection report you already pay for gives you the system pages. The rest is a phone list.

Frequently asked questions

Who handles fire safety plan approval in Ontario?

The Chief Fire Official for the municipality approves the plan under Ontario Fire Code Division B Section 2.8. In Windsor that is Windsor Fire & Rescue Services, and in Chatham-Kent it is Chatham-Kent Fire & Rescue. Approval applies to the building as described in the plan. A material change to the building or its systems calls for revised pages.

Is there a fire safety plan template for Ontario?

Many Ontario fire departments publish a fire safety plan template or guideline on their website, and the format is similar across the province. A template is a starting point. The content still has to match your building and be approved by the Chief Fire Official before it counts under Section 2.8.

How often does a fire safety plan have to be reviewed?

Ontario Fire Code Division B Section 2.8 requires a review at intervals of not more than 12 months. Review it sooner after a change of ownership, a new tenant, a change to a fire protection system or staff turnover. Windsor Fire & Rescue Services asks for updated contact pages every year.

Does the fire safety plan have to be kept on site?

Yes. The plan is kept in the building where supervisory staff and the fire department can get to it, and the emergency procedures are posted for occupants. Keep your fire drill and staff instruction records with it. Ontario Fire Code Division C Section 1.1.2 requires two years of records, and Windsor asks to see them on site.

What happens if the fire department finds the plan out of date?

The fire prevention officer is entitled to ask you to bring the plan current. They can also issue an inspection order under the Fire Protection and Prevention Act, 1997, and an order sets a deadline. Updating the plan and sending the revised pages for approval is how you close it.

Is an approved fire safety plan not already compliant?

Approval is a point in time. The Fire Code requires the plan to be kept current and reviewed within every 12 months. A plan approved in 2019 and untouched since is out of date on paper, even though it was once fine.

Red Seal has done more than 3,000 fire inspections in the last few years across Windsor-Essex, Chatham-Kent, Sarnia-Lambton and London. The system lists and photos in every report are what the plan’s system pages are built from. Every customer gets an online portal with every past report, so the pages you need for the annual update are one login away.

Bring your fire safety plan current before the next inspection. Send your building address to Red Seal and get a fixed-fee inspection quote within 24 hours. Get a fixed-fee quote or call 548-888-FIRE (3473).

Red Seal Fire Protection inspects, tests and repairs fire sprinkler, fire alarm, fire extinguisher, fire pump and backflow systems for commercial, industrial and multi-residential buildings in Windsor-Essex, Chatham-Kent, Sarnia-Lambton and London, Ontario.

Build Your Custom Fire Safety Plan

At Red Seal Fire Protection, we understand that every property has unique fire safety needs. Our experts work closely with you to assess your specific requirements, risks, and budget, creating a tailored fire safety plan that provides comprehensive protection while aligning perfectly with your business operations and goals.